Main
| Product or component type | Miniature circuit-breaker |
| Device application | Distribution |
| Poles description | 1P/2P/3P/4P |
| Number of protected poles | 1/2/3/4 |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 6kA |
Complementary
| rated operational voltage (Ue) | 1P:230/400V; 2P/3P/4P: 400V | |
| Control type | Toggle | |
| Local signalling | ON/OFF indication | |
| Mounting mode | Clip-on | |
| Mounting support | DIN rail 35mm | |
| Colour | Grey | |
|
Endurance (O-C) |
Electrical | 10,000 cydes |
| Mechanical durability | 20,000 cycles | |
Environment
| Standards | IEC 60947-2 |
| IP degree of protection | IP40 for modular enclosure conforming to IEC 60529 |
| IP20 conforming to IEC 60529 | |
| Operating altitude | 2000m |
| Ambient air temperature for operation | -35°C to +70°C |
| Ambient air temperature for storage | -40°C to +85°C |
Connection
| Rating | Tightening torque | Copper cables | |
| Rigid | Flexible or ferrule | ||
| 1 to 25 A | 2 N . m | 1 to 25 mm2 | 1 to 16 mm2 |
| 32 to 63 A | 2.5 N . m | 1 to 35 mm2 | 1 to 25 mm2 |
Product numbers
| Type | Width 9 mm modules | ||
| 1P/2P/3P/4P | Rating(ln) | C Curve | 2 |
![]() |
1A | TRMX1-63/1/C1 | |
| 3A | TRMX1-63/1/C3 | ||
| 5A | TRMX1-63/1/C5 | ||
| 6A | TRMX1-63/1/C6 | ||
| 10A | TRMX1-63/1/ | ||
| 16A | C10TRMX1-63/1/ | ||
| 20A | C16TRMX1-63/1/ | ||
| 25A | C20TRMX1-63/1/ | ||
| 32A | C25TRMX1-63/1/ | ||
| 40A | C32TRMX1-63/1/ | ||
| 50A | C40TRMX1-63/1/ | ||
| 63A | C50TRMX1-63/1/ | ||